The Power Supply is used for the operating voltage supply of the ISYGLT BUS components. When dimensioning the Power Supply, the maximum current values of the individual modules must be added. This is very easy to calculate via the parts list in the ProgramDesigner after the modules have been created.
Electrical Data
Operating voltage (primary) | 230V AC +/-10% 48/63Hz |
Output voltage | 24-28V DC adjustable, tolerance +/-3% |
Output current |
2.5A short-circuit proof, electronically protected current limitation 3.1A short-circuit current 3.5A |
Efficiency ratio | 85-90% |
Minimum load | 0mA |
Residual ripple | 35mVss |
No-load power loss | 0.9W |
Connection | screw terminals 2.5mm² |
Operating temperature | -10...+50°C |
Storage temperature | -25...+70°C |
Humidity | 0...90 % r.h. non-condensing |
Protection class | in non-installed state IP20 |
Design, Dimensions, Weight
Design | DIN rail-mounting plastic housing light grey, snap-on on 35mm DIN rail 4 HP |
Dimensions | 72x93x68mm |
Weight | 350g |
Changed design from fall 2024
Design | DIN rail-mounting plastic housing light grey, snap-on on 35mm DIN rail 3 HP |
Dimensions | 54x95x69mm |
Weight | 210g |
New
Sale
NT24V/2,5A-S
Article no.: 80030025