DA-04-VM2
Article no.: 80027004
-
kostenlose Anfrage / free request
from 1 € 0.00 € 0.00
The Analog Output Module is designed for colour temperature control. For this 2x 2 independent analog outputs (1-10V) are available for the control of 2 lights. The lamps are each equipped with a warm tone and a cold tone lamp. The light curves are conveniently optimised using the parameterisation tool in ProgramDesinger. During programming, the first channel is provided for brightness (AA*.1 and AA*.3) and the second channel (AA*.2 and AA*.4) for colour temperature (intensity between the cold white and warm white light colours). The analog outputs are then calculated in the values of the module and automatically control the intensity ratio between the two light sources (cold white and warm white).
The outputs have an output voltage range from 0(1) to 10V with 8 bit resolution.
The voltage outputs are galvanically isolated from the subnet and the operating voltage of the module. There is no potential separation between the 4 outputs. The outputs can be loaded as current source or current sink with 20mA per output. The 0-10V and 1-10V control is easily possible with this module.
The module DA-04-VM2 can be set from speed calculation to absolute time calculation by parameterisation per channel.
The following functions can be performed independently by the DA module:
Operating voltage | 18V to 35V DC or 18V to 27V AC |
Current consumption |
max. 120mA at 35V and full load of the outputs max. 200mA at 18V and full load of the outputs |
Output voltage | 4 analog channels, 8 bit resolution 0-10V |
Output current | 20mA per channel, operation as current source or current sink (total 80mA) |
Isolation voltage | 300V (subnet / analog outputs) |
Subnet (RS-485) | max. 5.6V limitation by Z-diodes |
Connection | screw terminals pluggable and P-COM connector |
Operating temperature | -10...+50°C |
Storage temperature | -25...+70°C |
Humidity | 0...85% r. h. non-condensing |
Protection class | IP30 |
8-pole DIP switch for setting the ISYGLT BUS address (0-127) is located under the cover of the module.
LED | Designation | State | Meaning |
---|---|---|---|
red | Power | Off | No operating voltage |
On | Operating voltage, no error | ||
yellow | BUS | Off / On | Error BUS |
blinking | Interference-free data transmission via the BUS line | ||
green | Regeln | blinking | Signals the regulation of the outputs (LED blinks until the desired final value is reached) |
In the ISYGLT ProgramDesigner there are various parameterisation possibilities:
=Ub | Operating voltage |
0V | 0V Operating voltage |
A | BUS A (subnet RS-485) |
B | BUS B (subnet RS-485) |
UA1 | Analog output channel 1 |
GND | Reference potential (ground) for analog outputs (4x internally connected) |
UA2 | Analog output channel 2 |
GND | Reference potential (ground) for analog outputs (4x internally connected) |
E | Emergency operation input |
UA3 | Analog output channel 3 |
GND | Reference potential (ground) for analog outputs (4x internally connected) |
UA4 | Analog output channel 4 |
GND | Reference potential (ground) for analog outputs (4x internally connected) |
Article no.: 80027004