Skip to main content Skip to page footer

Universal Button Interface TS-U1

The TS-U1 Button Interface is used for coupling application modules or button sensors to the ISYGLT-BUS.

Quick Facts

  1. coupling of button sensors
  2. 2-8 inputs (buttons)
  3. 2-8 outputs (LED red, green, integrated in button attachment)

The TS-U1 Button Interface is used for coupling application modules or button sensors to the ISYGLT-BUS. With the coupler, the LevySidus button sensor attachments, for example, can be easily operated in the ISYGLT-BUS with the full range of functions. We can also offer you button sensors from LevySidus. If you need couplers for button sensors of other manufacturers, please contact us specifically.

Electrical Data

Operating voltage 12V-35V DC, 12V-27V AC
Current consumption 25mA at 24V (5 LEDs on)
Subnet (RS-485) max. 5.6V limitation by Z-diodes
Connection Screw terminals 2.5mm² for BUS
Dimensions LxWxH 72x72x24mm
Operating temperature -10°C to +50°C
Storage temperature -25°C to +70°C
Humidity 0-85 % r.h. non-condensing
Protection class IP 00

Design, Dimensions, Weight

Design PCB on mounting plate for standard flush-mounted box
Dimensions LxWxH 72x72x24mm
Weight 55g

Ordering Data and Conformity

Type designation TS-U1
Article no. 80023210
Make ISYGLT
Conformity CE

Tender Documents

Instruction Manuals

Technical Drawings

Wiring Diagrams

DIP switch

8-pole DIP switch for setting the ISYGLT BUS address (0-127) is located on the back of the module.


Function Indicators (LEDs on the Module)

LEDDesignationStateMeaning
yellowBUSOffNo operating voltage
OnOperating voltage
blinkingInterference-free data transmission via the BUS line
fast blinkingNo parameters in the module

Parameterisation with ProgramDesigner

In the ISYGLT ProgramDesigner there are various parameterisation possibilities:

  • Parameterisation of the button sensor

Pin Assignment

4-pole plug back side

=Ub Operating voltage
0V 0V Operating voltage
A BUS A (Subnet RS-485)
B BUS B (Subnet RS-485)

Additional Equipment

  • ISYGLT - TS-U1 button print for GIRA button sensor UNI (80023220)

To top

New Sale
TS-U1-F_bild72.jpg

TS-U1

Article no.: 80023210

The TS-U1 Button Interface is used to connect application modules or pushbutton sensors to the ISYGLT BUS.