4-way Switching Actuator I/O-04H-230V-16A

I/O module with 4 optocoupler inputs 12-48V AC/DC and 4 relay outputs 230V/16A with manual lever. Wide range of parameterisable extra functions.

Quick Facts

  1. 4 binary inputs 12-48V
  2. 4 relay outputs 230V/16A
  3. Emergency and logic functions
  4. Manual control option
  5. Switching light
  6. Circuits remain in last state in case of voltage failure

The I/O module I/O-04H-230V-16A has been designed for applications where manual intervention is necessary or where the state of the relays must be maintained in the event of a BUS or power failure.

It is possible to switch 4 circuits with a maximum of 230V/16A. The phase position of the individual fuses is arbitrary. 4 optocoupler inputs 12-48V on a common counter potential are available as inputs.

All inputs and outputs can be parameterized in the module for different functions and are freely programmable in the functions via the ISYGLT ProgramDesigner software.

To protect the module from dust and unwanted operations, it is closed with a transparent lid. A screwdriver is required for manual operation.

  • The output relays can also be switched manually without programming (commissioning, service, maintenance...).
  • The relay position is maintained even if the supply voltage is interrupted.
  • Each individual output of the emergency module can be parameterised for the operating modes BUS operation, BUS failure, emergency operation (DIP1 ON).
  • The feedback LEDs can indicate the status of the inputs or outputs.
  • Due to the extensive parameter setting options, the module can also be used as a stand-alone module.

Electrical Data

Operating voltage 16V to 35V DC resp. 16V to 27V AC
Current consumption 200mA at 24V DC
Inputs 4x 12-48V AC/DC, input current per input 5mA at 24V
Outputs 4x relay contact
max. switching voltage 440V AC
max. switching current 20A >> (terminal max. 16A !)
mech. life 1.000.000 cycles
load capacity:
pure ohm's 16A
incandescent lamps 3500W (max. 30.000 cycles)
fluorescent lamps uncompensated 3500W (max. 30.000 switching cycles)
fluorescent compensated 2500W/200uF (max. 30.000 switching cycles)
high voltage halogen 3500W (max. 30.000 switching cycles)
low voltage halogen via transformer 2000VA (max. 30.000 switching cycles)
ECGs depending on manufacturer,
switch-on current 100A < 20ms
! The inrush current of electronic ballasts is up to 100 times the rated current !!
minimum contact load: 500mW, min. 10V, min. 5mA
Subnet (RS-485) max. 5.6V limitation by Z-diodes
Connection screw terminals 2.5mm² pluggable
Operating temperature -10...+50°C
Storage temperature -25...+70°C
Humidity 0...85 % r.h. non-condensing
Protection class when not installed IP30

Design, Dimensions, Weight

Design DIN rail-mounting plastic housing light grey, snap-on on 35mm DIN rail 6 HP
Dimensions WxHxD 106x90x59mm
Weight 325g

Ordering Data and Conformity

Type designation I/O-04H-230V-16A
Article no. 80022364
Make ISYGLT
Conformity CE

DIP switches

8-pole DIP switch for setting the ISYGLT BUS address (0-127) is located under the cover of the module.

Special function DIP switch 1

DIP-1 Setting
OFFBUS operation
ONEmergency operation (see parameterization options)

Function Indicators (LEDs on the Module)

LED DesignationState Meaning
red POWEROff No operating voltage
OnOperating voltage, no error
yellowBUSOff / OnError BUS
blinkingInterference-free data transmission via the BUS line
4x green Output 1-4Off Output inactive (parameterizable)
On Output active (parameterizable)
4x yellowInput 1-4Off Input inactive
On Input active

Parameterisation with ProgramDesigner

The ISYGLT ProgramDesigner offers a wide range of parameterisation options:

  • Definition of the functions in the operating modes: BUS operation, BUS failure, emergency operation
  • Function assignment per output
  • Synchronization conditions per output
  • Definition of the 4 LEDs for feedback of the outputs

Pin Assignment

4-pole plug top right

Ub Operating voltage
0V Operating voltage
A Subnet (BUS A, RS-485)
B Subnet (BUS B, RS-485)

2x P-COM Ports

P-COM Subnet and operating voltage

5-pole plug top left

CE Common f. E1-E4
E1 Input 1
E2 Input 2
E3 Input 3
E4 Input 4

6-pole plug bottom left

Free  
Free  
A1 Output 1
C.1 Common f. A1
A2 Output 2
C.2 Common f. A2

6-pole plug bottom right

A3 Output 3
C.3 Common f. A3
A4 Output 4
C.4 Common f. A4
Free  
Free