Skip to main content Skip to page footer

8-way Switching Actuator I/O-08D-230V-16A

I/O module with 8 optocoupler inputs 230V AC and 8 relay outputs 230V/16A. Special functions: 1 emergency input, emergency operation circuit.

Quick Facts

  1. 8 binary inputs 230V
  2. 8 relay outputs 230V/16A
  3. Inputs and outputs in the functions freely and independently programmable
  4. Special function: Emergency operation
  5. Control of light circuits
  6. 230V push-button circuits can be switched on directly
  7. Quiet switching

The I/O module I/O-08D-230V-16A can be used to switch 8 circuits with a maximum of 230V/16A. The phase position of the individual fuses is arbitrary. 8 optocoupler inputs 230V on a common counter potential are available as inputs. The functions of all inputs and outputs can be freely programmed via the software.

From production 2015, the modules will be available with the following parameterizable functions:

  • Status of the output relays after Power ON
  • Definition of inputs as currentless OFF or ON
  • Definition of the functions of the BUS inputs
  • Definition of the functions in the operating modes: BUS, BUS failure and emergency operation
  • Safety functions for motor controls (limit switch settings, interlocks, activation times definable, switch-on times)
  • Indication of defined pulse times on the relays
  • Definition of the display LEDs on the module (display inputs or outputs, BUS error, operating mode, running light)

Electrical Data

Operating voltage 16V to 35V DC resp. 16V to 27V AC
Current consumption 16V DC = 400mA, 24V DC = 250mA, 35V DC = 165mA
16V AC = 380mA, 24V AC = 220mA, 27V AC = 190mA (all relays energized)
Inputs 8x 230V AC (same phase!), input current per input 1mA
Outputs 8x relay contact 250V AC (DC max. 25V!)
Load capacity:
pure ohm's 16A
incandescent lamps 10A
fluorescent lamps uncompensated 6A
fluorescent lamps compensated 4A
low voltage halogen via transformer 10A
phase motor 0.55kW
ECGs depending on manufacturer,
inrush current 100A < 20ms
! The inrush current of electronic ballasts is up to 100 times the rated current !!
Minimum contact load: 500mW, min. 10V, min. 5mA
Subnet (RS-485) max. 5.6V limitation by Z-diodes
Connection screw terminals 2.5mm², inputs and BUS pluggable
From production 2010 all terminals are pluggable!
Operating temperature -10...+50°C
Storage temperature -25...+70°C
Humidity 0...85 % r.h. non-condensing
Protection class when not installed IP30

Design, Dimensions, Weight

Design DIN rail-mounting plastic housing light grey, snap-on on 35mm DIN rail 9 HP
Dimensions WxHxD 159x90x59mm
Weight 430g

Ordering Data and Conformity

Type designation I/O-08D-230V-16A
Article no. 80022468
Make ISYGLT
Conformity CE

DIP switches

8-pole DIP switch for setting the ISYGLT BUS address (0-127) is located under the cover of the module.

Special function DIP switch 1

DIP-1 Setting
OFFBUS operation
ONEmergency operation

Function Indicators (LEDs on the Module)

LED DesignationState Meaning
red POWEROff No operating voltage
OnOperating voltage, no error
yellowBUSOff / OnError BUS
blinkingInterference-free data transmission via the BUS line
8x green A1-A8Off Output inactive
On Output active

Parameterisation with ProgramDesigner

The ISYGLT ProgramDesigner offers a wide range of parameterisation options:

  • Preset behavior after PowerOn
  • Optocoupler inputs: polarity and debouncing
  • Assign BUS inputs
  • BUS operation
  • BUS failure operation
  • Emergency operation
  • Security features

Pin Assignment

9-pole plug top left

E1 Input 1
E2 Input 2
E3 Input 3
E4 Input 4
E5 Input 5
E6 Input 6
E7 Input 7
E8 Input 8
CE.1 Common f. E1-E8

4-pole plug top right

Ub Operating voltage
0V Operating voltage
A Subnet (BUS A, RS-485)
B Subnet (BUS B, RS-485)

2x P-COM Ports

P-COM Subnet and operating voltage

Special input emergency:

If 230V is applied to this input, all relays switch on (operating voltage must be present!).

6-pole plug bottom left

E 230V Emergency input
CE.2 N Emergency input
A1 Output 1
C.1 Common f. A1
A2 Output 2
C.2 Common f. A2

6-pole plug bottom centre

A3 Output 3
C.3 Common f. A3
A4 Output 4
C.4 Common f. A4
A5 Output 5
C.5 Common f. A5

6-pole plug bottom right

A6 Output 6
C.6 Common f. A6
A7 Output 7
C.7 Common f. A7
A8 Output 8
C.8 Common f. A8