I/O-08D-230V-16A
Article no.: 80022468
-
kostenlose Anfrage / free request
from 1 € 0.00 € 0.00
The I/O module I/O-08D-230V-16A can be used to switch 8 circuits with a maximum of 230V/16A. The phase position of the individual fuses is arbitrary. 8 optocoupler inputs 230V on a common counter potential are available as inputs. The functions of all inputs and outputs can be freely programmed via the software.
From production 2015, the modules will be available with the following parameterizable functions:
Operating voltage | 16V to 35V DC resp. 16V to 27V AC |
Current consumption |
16V DC = 400mA, 24V DC = 250mA, 35V DC = 165mA 16V AC = 380mA, 24V AC = 220mA, 27V AC = 190mA (all relays energized) |
Inputs | 8x 230V AC (same phase!), input current per input 1mA |
Outputs |
8x relay contact 250V AC (DC max. 25V!) Load capacity: pure ohm's 16A incandescent lamps 10A fluorescent lamps uncompensated 6A fluorescent lamps compensated 4A low voltage halogen via transformer 10A phase motor 0.55kW ECGs depending on manufacturer, inrush current 100A < 20ms ! The inrush current of electronic ballasts is up to 100 times the rated current !! Minimum contact load: 500mW, min. 10V, min. 5mA |
Subnet (RS-485) | max. 5.6V limitation by Z-diodes |
Connection |
screw terminals 2.5mm², inputs and BUS pluggable From production 2010 all terminals are pluggable! |
Operating temperature | -10...+50°C |
Storage temperature | -25...+70°C |
Humidity | 0...85 % r.h. non-condensing |
Protection class | when not installed IP30 |
8-pole DIP switch for setting the ISYGLT BUS address (0-127) is located under the cover of the module.
LED | Designation | State | Meaning |
---|---|---|---|
red | POWER | Off | No operating voltage |
On | Operating voltage, no error | ||
yellow | BUS | Off / On | Error BUS |
blinking | Interference-free data transmission via the BUS line | ||
8x green | A1-A8 | Off | Output inactive |
On | Output active |
The ISYGLT ProgramDesigner offers a wide range of parameterisation options:
E1 | Input 1 |
E2 | Input 2 |
E3 | Input 3 |
E4 | Input 4 |
E5 | Input 5 |
E6 | Input 6 |
E7 | Input 7 |
E8 | Input 8 |
CE.1 | Common f. E1-E8 |
Ub | Operating voltage |
0V | Operating voltage |
A | Subnet (BUS A, RS-485) |
B | Subnet (BUS B, RS-485) |
Special input emergency:
If 230V is applied to this input, all relays switch on (operating voltage must be present!).
E | 230V Emergency input |
CE.2 | N Emergency input |
A1 | Output 1 |
C.1 | Common f. A1 |
A2 | Output 2 |
C.2 | Common f. A2 |
A3 | Output 3 |
C.3 | Common f. A3 |
A4 | Output 4 |
C.4 | Common f. A4 |
A5 | Output 5 |
C.5 | Common f. A5 |
Article no.: 80022468