Panel Module I/O-08T-24V

The I/O Panel Module I/O-08T-24V can be used to connect 8 buttons and 8 signal lamps to the ISYGLT BUS system.

Quick Facts

  • 8 optocoupler inputs
  • 8 relay outputs, 24V/300mA
  • For 8 buttons with feedback signal
  • Panels
  • External control panels

With the I/O Panel Module I/O-08T-24V 8 buttons and 8 signal lamps can be connected to the ISYGLT BUS system. 8 relay outputs max. 48V/300mA are available as outputs and 8 optocoupler inputs 12-48V as inputs, each on a common counter potential. The functions of all inputs and outputs are freely programmable via the software.

Electrical Data

Operating voltage 12V to 35V DC or 12V to 27V AC
Current consumption 12V DC = 180mA, 24V DC = 80mA, 35V DC = 55mA
12V AC = 105mA, 24V AC = 70mA, 27V AC = 65mA
(all relays energized in each case)
Inputs 12-48V AC/DC, input current per input 5mA at 24V; Ue max. 48V
Outputs max. 48V/300mA per output
Subnet (RS-485) max. 5.6V limitation by Z-diodes
Connection screw terminals 1.0mm², or post plug for flat ribbon cable
Operating temperature -10...+50°C
Storage temperature -25...+70°C
Humidity 0...85 % r.h. non-condensing
Protection class in non-installed state IP00

Design, Dimensions, Weight

Design PCB without housing, snap-on on 35mm DIN rail
Dimensions LxWxH 100x70x30mm
Weight 90g

Ordering Data and Conformity

Type designation I/O-08T-24V
Article no. 80021100
Make ISYGLT
Conformity CE

Tender Documents

Instruction Manuals

Wiring Diagrams

DIP switches

8-pole DIP switch for setting the ISYGLT BUS address (0-127) is located on the module.


Function Indicators (LEDs on the Module)

LEDDesignationStateMeaning
redPOWEROffNo operating voltage
OnOperating voltage, no error
yellowBUSOff / OnError BUS
blinkingInterference-free data transmission via the BUS line

Pin Assignment

8-pole terminal left

B Subnet (BUS B, RS-485)
B Subnet (BUS B, RS-485)
A Subnet (BUS A, RS-485)
A Subnet (BUS A, RS-485)
0V Operating voltage 0V
0V Operating voltage 0V
Ub Operating voltage
Ub Operating voltage

6-pole post plug for flat ribbon cable wiring

1 +Ub
2 +Ub
3 0V
4 0V
5 BUS A
6 BUS B

8-pole terminal bottom left

A8 Output 8
A7 Output 7
A6 Output 6
A5 Output 5
A4 Output 4
A3 Output 3
A2 Output 2
A1 Output 1

12-pole terminal bottom right

C.A Common Outputs
+Ub +Ub-1V
0V 0V
C.E Common Inputs
E8 Input 8
E7 Input 7
E6 Input 6
E5 Input 5
E4 Input 4
E3 Input 3
E2 Input 2
E1 Input 1

20-pole post plug for flat ribbon cable wiring

1 free
2 +Ub -1V
3 Input 1
4 Output 1
5 Input 2
6 Output 2
7 Input 3
8 Output 3
9 Input 4
10 Output 4
11 Input 5
12 Output 5
13 Input 6
14 Output 6
15 Input 7
16 Output 7
17 Input 8
18 Output 8
19 0V
20 +Ub -1V
IO-08T-24V_bild72.jpg

I/O-08T-24V

Article no.: 80021100

With the I/O tableau module I/O-08T-24V, 8 buttons and 8 indicator lights can be connected to the ISYGLT BUS system.
+ shipping costs
  • kostenlose Anfrage / free request
    from 1 € 0.00 € 0.00