I/O-08E-24V-1A
Article no.: 80021001
-
kostenlose Anfrage / free request
from 1 € 0.00 € 0.00
The I/O module I/O-08E-24V-1A was developed for applications with high switching frequencies. The Photomos relays used can be used to switch 8 circuits with a maximum of 5-35V DC or 5-27V AC / 1A.
8 optocoupler inputs 12-48V on a common counter potential are available as inputs. The functions of all inputs and outputs are freely programmable via the software.
Operating voltage | 16V to 35V DC or 16V to 27V AC |
Current consumption | 50mA at 24V DC (all relays are energized) |
Inputs | 8x 12-48V AC/DC, input current per input 5mA at 24V |
Outputs | 8x Photomos relay, 5-35V DC or 5-27V AC / 1A each output |
Subnet (RS-485) | max. 5.6V limitation by Z-diodes |
Connection | screw terminals 1.5mm², inputs and BUS pluggable, BUS connector |
Operating temperature | -10°C to +50°C |
Storage temperature | -25°C to +70°C |
Humidity | 0...85 % r.h. non-condensing |
Degree of protection | in not installed state IP30 |
8-pole DIP switch for setting the ISYGLT BUS address (0-127) is located under the cover of the module.
LED | Designation | State | Meaning |
---|---|---|---|
red | POWER | Off | No operating voltage |
On | Operating voltage, no error | ||
yellow | BUS | Off / On | Error BUS |
blinking | Interference-free data transmission via the BUS line | ||
8x green | A1-A8 | Off | Output inactive |
On | Output active |
The ISYGLT ProgramDesigner offers a wide range of parameterisation options:
Ub | Operating voltage |
0V | Operating voltage |
A | Subnet (BUS A, RS-485) |
B | Subnet (BUS B, RS-485) |
CE.1 | Common for E1-E8 |
E1 | Input 1 |
E2 | Input 2 |
E3 | Input 3 |
E4 | Input 4 |
E5 | Input 5 |
E6 | Input 6 |
E7 | Input 7 |
E8 | Input 8 |
C.1 | Common for output 1 |
A1 | Output 1 |
C.2 | Common for output 2 |
A2 | Output 2 |
C.3 | Common for output 3 |
A3 | Output 3 |
C.4 | Common for output 4 |
A4 | Output 4 |
Article no.: 80021001