8-way Switching Actuator I/O-08E-24V-1A

I/O module with 8 binary inputs and 8 Photomos relay outputs for applications with increased switching frequencies.

Quick Facts

  1. 8 binary inputs
  2. 8 Photomos relays, 5-35V DC or 5-27V AC / 1A
  3. Door and sluice control
  4. Blinking lights

The I/O module I/O-08E-24V-1A was developed for applications with high switching frequencies. The Photomos relays used can be used to switch 8 circuits with a maximum of 5-35V DC or 5-27V AC / 1A. 
8 optocoupler inputs 12-48V on a common counter potential are available as inputs. The functions of all inputs and outputs are freely programmable via the software.

Electrical Data

Operating voltage 16V to 35V DC or 16V to 27V AC
Current consumption 50mA at 24V DC (all relays are energized)
Inputs 8x 12-48V AC/DC, input current per input 5mA at 24V
Outputs 8x Photomos relay, 5-35V DC or 5-27V AC / 1A each output
Subnet (RS-485) max. 5.6V limitation by Z-diodes
Connection screw terminals 1.5mm², inputs and BUS pluggable, BUS connector
Operating temperature -10°C to +50°C
Storage temperature -25°C to +70°C
Humidity 0...85 % r.h. non-condensing
Degree of protection in not installed state IP30

Design, Dimensions, Weight

Design DIN rail-mounting plastic housing light grey, snap-on on 35mm DIN rail 6 HP
Dimensions WxHxD 106x90x59mm
Weight 230g

Ordering Data and Conformity

Type designation I/O-08E-24V-1A
Article no. 80021001
Make ISYGLT
Conformity CE

DIP switch

8-pole DIP switch for setting the ISYGLT BUS address (0-127) is located under the cover of the module.

Special function DIP switch 1

DIP-1 Setting
OFFBUS operation
ONEmergency operation

Function Indicators (LEDs on the Module)

LED DesignationState Meaning
red POWEROff No operating voltage
OnOperating voltage, no error
yellowBUSOff / OnError BUS
blinkingInterference-free data transmission via the BUS line
8x green A1-A8Off Output inactive
On Output active

Parameterisation with ProgramDesigner

The ISYGLT ProgramDesigner offers a wide range of parameterisation options:

  • Preset behaviour after PowerOn
  • Optocoupler inputs: polarity and debouncing
  • Assign BUS inputs
  • BUS operation
  • BUS failure operation
  • Emergency operation
  • Safety functions

Pin Assignment

4-pole plug top left

Ub Operating voltage
0V Operating voltage
A Subnet (BUS A, RS-485)
B Subnet (BUS B, RS-485)

2x P-COM ports

P-COM Subnet and operating voltage

9-pole plug below left

CE.1 Common for E1-E8
E1 Input 1
E2 Input 2
E3 Input 3
E4 Input 4
E5 Input 5
E6 Input 6
E7 Input 7
E8 Input 8

8-pole plug top right

C.1 Common for output 1
A1 Output 1
C.2 Common for output 2
A2 Output 2
C.3 Common for output 3
A3 Output 3
C.4 Common for output 4
A4 Output 4

8-pole plug below right

C.5 Common for output 5
A5 Output 5
C.6 Common for output 6
A6 Output 6
C.7 Common for output 7
A7 Output 7
C.8 Common for output 8