I/O-22E-S-PNP
Article no.: 80021242
-
kostenlose Anfrage / free request
from 1 € 0.00 € 0.00
The built-in I/O Module is used to connect sensors such as piezo buttons, reflection light buttons with PNP transistor output or door contacts type lfm-electronics NG 5001 and magnetic valves to the subnet. The module can be used to transfer 2 commands to the BUS system and to issue 2 commands. The sensors or magnetic valves are connected by means of assembled cable connectors.
Example: (see Wiring Diagrams) 2 reflection light buttons with PNP transistor output and 2 magnetic valves
Operating voltage | 12V to 30V DC |
Current consumption | 25mA at 24V |
Inputs | 2x 12-27V DC, 5mA via optocoupler (4.7kOhm) for PNP outputs |
Outputs | 2x transistor outputs for valves, +Ub, max. 1A |
Subnet (RS-485) | max. 5.6V limitation by Z-diodes |
Connection | screw terminals 2.5mm² for BUS, cable connector for sensors and valves |
Operating temperature | -10°C to +50°C |
Storage temperature | -25°C to +70°C |
Humidity | 0...85 % r.h. non-condensing |
Protection class | IP20 |
LED | Designation | State | Meaning |
---|---|---|---|
red | POWER | Off | No operating voltage |
On | Operating voltage, no error | ||
yellow | BUS | Off / On | Error BUS |
blinking | Interference-free data transmission via the BUS line | ||
2x green | Channel 1/2 | Off | Output inactive |
On | Output active |
Ub | Operating voltage |
0V | Operating voltage 0V |
A | Subnet (BUS A, RS-485) |
B | Subnet (BUS B, RS-485) |
E1 | Input 1 | E2 | Input 2 | Caution! Ex.1 and Ex.2 are internally connected to GND, i.e. +Ub must be switched |
ws | +24V | ws | +24V | |
br | 0V | br | 0V | |
gn | E1 | gn | E2 | |
ge | ge |
Article no.: 80021242