Single-Room Temperature Controller ER-01U-G1

The ER-01U-G1 Single-Room Temperature Controller ensures temperature management for a wide range of room requirements. The room controller is integrated in the control unit.

Quick Facts

  • Setpoint adjustment via rotary knob
  • Comfort button
  • Connection window contact
  • Output for controlling actuators
  • Temperature management
  • Single-Room control
  • Heating radiators
  • Cooling ceilings

The ER-01U-G1 Single-Room Controller ensures temperature management for a wide range of room requirements. Economic energy utilisation of radiator heating systems and underfloor heating is achieved by demand-oriented control for each room. The communication-capable controllers can be easily integrated into higher-level ISYGLT-BUS systems for building automation. The controller is programmed and configured very conveniently using our programming software ProgramDesigner (from version 3.40.3). In the communication network with the primary system, the controllers ensure that only as much energy as necessary is processed.

Heating radiators, cooling ceilings etc. are controlled by thermal, magnetic or electromotive actuators. The logical links, e.g. with presence sensors, window contacts, higher-level energy cut-off by the house technician or by time switching, are implemented in the Master Module of the ISYGLT BUS system.

The operating button is used for manual control of the desired operating mode. The current operating mode is indicated by LEDs.

  • Suitable for electromotive or electrothermal actuators (specify when ordering)
  • With one controller, radiator / underfloor heating and cooling ceilings can be operated simultaneously via the master module via a link.
  • Parameterisable to any ambient conditions
  • Management of 4 basic temperatures: Day, Night, Comfort and Frost protection
  • External setpoint setting by the Master Module possible
  • Integration option for presence sensors
  • Energy lockout through window contacts
  • Possibility to configure the setpoint slide (default +/- 3°C)
  • Forced flushing of the heating valves during the summer break 1x weekly
  • Alignment possibility of the temperature sensor

Single-Room Temperature Controller ON/OFF (energy lockout via the ISYGLT-BUS system)

The energy lockout is used to switch the controller to the energy-saving mode in the event of prolonged absence. Only as much energy is consumed to maintain the target temperature for frost protection. The setpoint temperature for frost protection can be freely parameterised. The "energy lockout" mode is signalled by the fact that all LEDs on the room controller are dark.

ON: All operating modes adjustable
OFF: All LEDs are dark. Setpoint temperature corresponds to setting for frost protection (freely parameterisable)

Day mode

In the "Day mode" operating mode, the setpoint temperatures for HEATING and COOLING are active in each case. A further subdivision into "Present", "Absent" and "Remote operation" is possible. The setpoint temperature for "Day mode and present" (comfort setpoint temperature) and "Day mode and absent" (day setpoint value) can be freely parameterised. In remote operation, the target temperature can be optionally set for each room via the ISYGLT-BUS system using the "RAUMREG" command.

Night mode

In the "Night mode" operating mode, the set temperatures for HEATING and COOLING are active. A further subdivision into "Present", "Absent" and "Remote operation" is possible. The setpoint temperature for "Night mode and Present" (comfort setpoint temperature) and "Night mode and Absent" (night setpoint value) can be freely parameterised. In remote operation, the target temperature can optionally be set for each room via the ISYGLT-BUS system using the RAUMREG command.

Frost protection

The "Frost protection" operating mode is active when the individual room temperature controller is switched off via the ISYGLT-BUS system, the window contact is active, or a room temperature is detected that is lower than the set "Frost protection" setpoint. The temperature for "Frost protection" can be freely parameterised.

Dew point alarm

The dew point alarm is only effective in conjunction with the "Cooling" operating mode. It is activated by a dew point sensor on the ISYGLT-BUS system.

Remote mode

The room temperature controllers can be selected via the ISYGLT-BUS system. The ACTUAL temperature can be called up via the ISYGLT-BUS system, the SET temperature specified and the control signal for the valve specified by the room temperature controller. On request, all functions of the room temperature controller can be called up and controlled via the ISYGLT-BUS system.

Comfort button on the intelligent unitary controller

The button controls the change between "Comfort temperature" and "Day or night mode". Each new button press cancels the previous status. This gives the room user the option of choosing between two different setpoint temperatures. The target temperatures can be freely parameterised for both operating modes. If the ISYGLT-BUS system is switched to night mode during the "Day and Present" operating mode (comfort temperature), the controller switches to the "Night and Absent" operating mode. If the ISYGLT-BUS system changes back to the "Day" operating mode, the controller remains in the "Absent" operating mode. The button can be locked to prevent tampering. This can be done permanently or only at certain times via the ISYGLT-BUS system. The operating modes can be set from the ISYGLT-BUS system via the BUS and can be confirmed. It is possible to set an operating mode via the ISYGLT-BUS system and then to lock the button in order to prevent manipulation, e.g. in schools etc. It is also possible to switch a room to another operating mode via the ISYGLT-BUS system and then leave the rest of the process to the room user via the button on the controller. The function is freely programmable and can be adapted to individual requirements.

The function of the comfort button depends on the operating mode:

Day mode and presence sensor locked:
Change between operating mode "Present" and "Absent" (change between two freely parameterisable set temperatures)

Control via the ISYGLT-BUS system:
From "Day mode+Absent" to "Night mode+Absent"
From "Night mode+Absent" to "Day mode+Absent"

Night mode and presence sensor locked:
The presence button has a veto function. Press to toggle between "Absent" and "Present" (1...255min). The controller then automatically returns to "Absent". The veto function can be repeated as often as required.

Control via the ISYGLT BUS system:
From "Day mode+Absent" to "Night mode+Absent"
From "Night mode+Absent" to "Day mode+Absent"

Day mode and presence sensor enabled:
Change between "Present" and "Absent".

Presence detector activates the "Present" operating mode when "Absent" is selected. When leaving the room and pressing the presence button, the presence detector is blocked for 1...255sec in order not to reactivate the "Present" operating mode.

Control via the ISYGLT BUS system:
From "Day mode+Absent" to "Night mode+Absent"
From "Night mode+Absent" to "Day mode+Absent"

Night mode and presence sensor enabled:
Change between "Present" and "Absent".

Presence detector activates the "Present" operating mode when "Absent" is selected. After the parameterizable time of 1...255min has elapsed, the system automatically switches to the "Absent" operating mode (retriggerable).

Control via the ISYGLT BUS system:
From "Day mode+Absent" to "Night mode+Absent"
From "Night mode+Absent" to "Day mode+Absent"

Electrical Data

Operating voltage 12-35V DC; 12-27V AC
Current consumption max. at 12V 30mA; at 24V 30mA; 35V 30mA (without load on the outputs)
Binary inputs Input E window contact connection (optocoupler input), direction of action programmable (5mA at 24V)
Analog output UA1
(ER-01U-G1A only)
0-10V for controlling the electromotive valve actuators with 0-10V interface max. 10 mA loadable
Switching output
(ER-01U-G1D only)
transistor output (PNP) max. Ub-1V / 0.3A
Output current for actuators max. 300mA (operating voltage -1V)
Alignment of actual value temperature ± 3K (via parameterisation software)
Adjustment range setpoint slide ± 0...3K (via parameterisation software)
Measuring element semiconductor sensor calibrated ± 0.5K
Subnet (RS-485) max. 5.6V limitation by Z-diodes
Connection screw terminals 1.5mm²
Operating temperature 0...+50°C
Storage temperature -25...+70°C
Humidity 0...85 % r.h. non-condensing
Protection class III
Protection degree installed IP20

Design, Dimensions, Weight

Design UP plastic housing suitable for GIRA-S-Color pure White
Dimensions HxWxD 70x70x20mm (+30mm in flush-mounted box)
Weight 90g

Ordering Data and Conformity

Type designation ER-01U-G1A (with analog output) / ER-01U-G1D (with digital output)
Article no. 80080151 / 80080152
Make ISYGLT
Conformity CE

DIP switch

8-pole DIP switch for setting the ISYGLT BUS address (0-127) on the module.


Function Indicators (LEDs on the Module)

LEDDesignationStateMeaning
yellow

BUS (under rotary knob)

OffNo operating voltage
OnError BUS. The controller operates independently of the ISYGLT-BUS system. Always in day mode, as no time information is transmitted.
blinkingInterference-free data transmission via the BUS line
greenPresentOnComfort temperature setpoint activated
(presence button or presence sensor)
greenAbsentOnController in standby mode. The current setpoint depends on the operating mode day or night.
yellowNight modeOnNight mode active
redFrost protectionOnRoom temperature < setpoint temperature frost protection. The state "Frost protection active" can be evaluated in the Master, the setpoint temperature frost protection can be parameterised.
redDew point alarmOnCurrent state of input E3 (dew point sensor). LED lights up when the input is active.

 

More detailed information on the function indicators and the operating mode indicators can be found in the instruction manual.


Parameterisation with ProgramDesigner

In the ISYGLT ProgramDesigner there are further parameterisation possibilities:

  • Target temperatures (Day/Night/Comfort)
  • Protective temperature
  • Compensation
  • Valve control
  • Times
  • Special features

One of the following functions can be output at the digital output (ER-01U-G1D) by parameterisation:

  • Digital output from Master
  • Output for radiator heater
  • Output for underfloor heating
  • Output for cooling unit
  • Load capacity: max. Ub-1V 300mA continuous load

Pin Assignment

8-pole plug (ER-01U-G1A)

Ub Operating voltage
0V Operating voltage
A Subnet (BUS A, RS-485)
B Subnet (BUS B, RS-485)
E Input window contact
UbV 24V supply of the actuator
GND 0V for actuator (operating voltage and control signal)
UaV Analog output 0-10V

8-pole plug (ER-01U-G1D)

Ub Operating voltage
0V Operating voltage
A Subnet (BUS A, RS-485)
B Subnet (BUS B, RS-485 )
E Input window contact
UbV 24V supply of the actuator
GND 0V for actuator (operating voltage and control signal)
UaV Digital output (+Ub-1V) PWM

Setpoint Slider

Using the rotary knob on the front panel, the setpoint can be changed by ±0-3K (parameterisable) in the "Day", "Night" and "Comfort" operating modes.
In the operating modes "Energy lockout" and "Remote mode", the setpoint slide valve is not taken into account. This ensures that the frost protection temperature cannot be reduced. Furthermore, it is ensured that the setpoint specified by the ISYGLT-BUS system is also approached. (The ISYGLT-BUS system does not know the position of the setpoint slider.)

Temperature Correction

A calibrated semiconductor sensor is used as the temperature sensor. If the room controller is installed at a location that does not have the same temperature as the occupied zone, the setpoint can be adjusted again using the parameterisation software (ProgramDesigner). Thus temperature gradients in the room can be compensated.

To top

Variants

  • with digital output: ER-01U-G1D
  • with analog output: ER-01U-G1A

To top

ER-01U-G1_bild72.jpg

ER-01U-G1D

Article no.: 80080152

The Single-Room Temperature Controller ER-01U-G1 ensures temperature management for a wide range of room requirements. The room controller is integrated in the operating unit.
+ shipping costs
  • kostenlose Anfrage / free request
    from 1 € 0.00 € 0.00
  • Click & Collect
    from 1 € 0.00 € 0.00
    Local pick-up
  • DHL
    from 1 € 0.00 € 5.90 Incl. 20.00% VAT
    Delivery within three days
  • DHL Express
    from 1 € 0.00 € 11.90 Incl. 20.00% VAT
    Delivery on the next day
  • Fedex
    from 1 € 0.00 € 6.90 Incl. 20.00% VAT
    Delivery within three days
  • TNT
    from 1 € 0.00 € 8.90 Incl. 20.00% VAT
    Delivery within three days