The Temperature Sensor TF-L is designed for connection to the ISYGLT modules TEMP-02U or ER-04U. It is supplied as a loose component. The measuring range of the sensor is -55°C to +105°C.
The following must be observed when mounting the sensor for room temperature measurement:
The sensor must be freely surrounded by the room air. Installation in the occupied zone approx. 1.5m high above the floor and at least 0.5m away from the next wall. Do not expose to direct sunlight. Do not mount on an external wall, in niches, behind curtains, near doors or near heat sources (lamps, fireplaces).
Electrical Data
Cable length | 0.3m heat resistant |
Measuring range | -55 to +105°C |
Measuring element | semiconductor sensor calibrated ± 0.5K |
Precision |
± 0,5°C in the range -15°C to +105°C ± 2°C in the range -55°C to -15°C |
Operating temperature | -55...+125°C |
Storage temperature | -55...+125°C |
Protection class | IP 65 |
New
Sale
TF-L
Article no.: 80081110
The Temperature Sensor TF-L is designed for connection to the ISYGLT modules TEMP-02U or ER-04U.