Preparation - interfaces
The UD-700-X2 is parameterized and operated in ISYGLT mode as usual via the BUS interface.
For DMX and standalone operation, a separate software is available. Communication from the PC to the dimmer is possible in 2 ways:
1. A USB Micro B connector is located under the cover. Connection via USB cable (USB type A to Micro B m/m)
or
2. via the terminals A and B of the dimmer, via RS-485 e.g. with a USB-to-serial RS-485 adapter.
If you are using the USB interface for the first time, the driver must be installed,
the connection from the dimmer to the PC must be established and the dimmer must be energized.
Start the software (download here), select the function "hardware connection" under "extras" and click on "test".
If a valid connection is detected, it is displayed in the "Port" field. Otherwise the message "communication port was not recognized" appears.
If the port is not detected, the line connection, DIP switch setting and dimmer must be checked again.
The basic functions of the program in the header line:
Function | Description |
New | Create new configuration (preset with default values) |
Opening | Call up an existing, saved configuration |
Save | Saving the current configuration |
Save as | Saving the current configuration under a different name |
Read parameter | Reading parameter data from the dimmer |
Write parameters | Transfer the current parameters from the registers to the dimmer |
<h4/>
Parameter basic setting
Here you will find basic settings for standalone and DMX operation.
Please note the DIP settings:
Operating mode setting for DMX-512 and standalone operation with DIP switches "A" to "D
DIP-A | DIP-B | Operating mode |
OFF | OFF | Automatic operating mode changeover, the start value is predefined with the PC program on the "basic setting" tab. |
ON | OFF | PAB phase section |
OFF | ON | PAN phase control |
ON | ON | NonDim |
DIP-C | DIP-D | Setting dimming characteristics such as min-max values, curves, etc. (PC program) |
OFF | OFF | Parameters of the 1st column ("basic settings" in the PC program UD-700-X2) |
ON | OFF | Parameters of the 2nd column ("basic settings" in the PC program UD-700-X2) |
OFF | ON | Parameters of the 3rd column ("basic settings" in the PC program UD-700-X2) |
ON | ON | Parameters of the 4th column (with preheating setting for ESL) ("basic settings" in PC program UD-700-X2) |
Traditional illuminants
Determining the maximum number of light sources that can be connected is relatively easy with traditional light sources - see table.
Power/ electricity | Loss transformer | UD-700-X2 per channel (700W) | UD-700-X2 parallel (1400W) | |
<header/> | Number of illuminants | |||
Halogen lamps 230V | ||||
Halogen lamp 20W | 20W | 35 | 70 | |
Halogen lamp 30W | 30W | 23 | 46 | |
Halogen lamp 46W | 46W | 15 | 30 | |
Halogen lamp 57W | 57W | 12 | 24 | |
Halogen lamp 77W | 77W | 9 | 18 | |
Halogen lamp 116W | 116W | 6 | 12 | |
Halogen R7s | ||||
Halogen R7s 48W | 48W | 14 | 29 | |
Halogen R7s 80W | 80W | 8 | 17 | |
Halogen R7s 120W | 120W | 5 | 11 | |
Halogen R7s 160W | 160W | 4 | 8 | |
Halogen R7s 230W | 230W | 3 | 6 | |
Halogen R7s 400W | 400W | 1 | 3 | |
Bulbs 230V | ||||
Bulb 15W | 15W | 46 | 93 | |
Bulb 25W | 25W | 28 | 56 | |
Bulb 40W | 40W | 17 | 35 | |
Bulb 60W | 60W | 11 | 23 | |
Bulb 100W | 100W | 7 | 14 | |
LV halogen lamps 12V | ||||
LV halogen lamp 10W | 10W | approx. 10% of | 63 | 126 |
LV halogen lamp 14W | 14W | approx. 10% of | 45 | 90 |
LV halogen lamp 20W | 20W | approx. 10% of | 31 | 63 |
LV halogen lamp 25W | 25W | approx. 10% of | 25 | 50 |
LV halogen lamp 33W | 33W | approx. 10% of | 19 | 38 |
LV halogen lamp 35W | 35W | approx. 10% of | 18 | 36 |
LV halogen lamp 48W | 48W | approx. 10% of | 13 | 26 |
LV halogen lamp 50W | 50W | approx. 10% of | 12 | 25 |
Fluorescent lamps with VIP90/2 | ||||
S/E 5W | 0,18A | 16 | 33 | |
S/E 7W | 0,175A | 17 | 34 | |
S/E 9W | 0,17A | 17 | 35 | |
S/E 11W | 0,16A | 18 | 37 | |
D/E 10W | 0,19A | 15 | 31 | |
D/E 13W | 0,165A | 18 | 36 | |
D/E 18W | 0,22A | 13 | 27 | |
D/E 26W | 0,315A | 9 | 19 | |
L 18W | 0,37A | 8 | 16 | |
L 24W | 0,34A | 8 | 17 | |
L 36W | 0,43A | 6 | 13 | |
L 58W | 0,67A | 4 | 8 | |
F 18W | 0,375A | 8 | 16 | |
F 24W | 0,345A | 8 | 17 | |
F 36W | 0,44A | 6 | 13 |
Retrofits - LED - energy saving lamps
The whole thing then becomes more complex with retrofit lamps (LED and ESL). The manufacturer's data sheet should be observed first. Is the light source dimmable? In which area can dimming be carried out? Which type of dimming (phase cut or phase cut) is recommended?
However, more precise information is often missing - the UD-700-X2 can be used to check this right away. This can be done directly in the plant, or in the planning stage in advance with individual light sources. When testing individual light sources, we recommend testing with several (3-5 pieces), as these light sources also have certain tolerances.
For simplicity's sake, here is an example with just one single OSRAM PARATHOM® PAR16 50 36° ADVANCED, which was measured at the test station with the UD-700-X2 and then the result checked on site at the customer's premises.
Execution of the test:
- Connect OSRAM LED to output 1
- Connect dimmer with USB cable to PC
- Connect dimmer to 230V voltage
- Start the "UD-700-X-PC-Testprogramm" software
- under "Extras" test and confirm the hardware connection
- Default setting: phase segment
- Now on the page "Dimmer Status" move the slider for channel 1 from minimum to maximum and observe the maximum current.
Here it can be seen that the highest operating current is 0.21A at approx. 90% dimming setting.
Phase angle cross-check mode: On the "Grundeinstellung" page, select "ANschnitt" in the "Betriebsart-Voreinstellung" on the right and click on "Parameter schreiben" at the top.
Here is the test in the Oszi function. Procedure as described above - Attention, the peak current here is 1.3A per LED illuminant!
<STRONG/>
Specification: Operating mode remains phase segment!
The dimmer is designed for a continuous operating current of 3A per channel. The peak currents may be 8A. This results in a calculated 8A / 0.4A = 20 LED lamps.
That would be the worst case.
The detected continuous peak current is 0.21A. Depending on the installation, the line resistance is also favourable, depending on the distance to the dimmer and the illuminants from each other.
That's why we use the mean value - 0.3A - as a basis - which corresponds to 26 LED light sources.
Our customer has a BAR counter with 28x50W halogen lamps = 1400W
Now it has been converted to the OSRAM PARATHOM™ PAR 16 50 35° (7W).
We have measured with the UD-700-X2 in the plant:
Peak current during measurement of the 4. Half period = 8.2A (28 pieces)
Continuous operating peak current = 4.2A
Test with phase angle control: Overcurrent >> automatic switch-over to phase segment
Conclusion:
The existing UD-500-M2 with UD-1000-S could be replaced by a channel of the UD-700-X2. At our discretion, sufficient reserves are available. The system can therefore be operated without hesitation.