The Power Supply is used for the operating voltage supply of the ISYGLT BUS components. When dimensioning the Power Supply, the maximum current values of the individual modules must be added. This is very easy to calculate via the parts list in the ProgramDesigner after the modules have been created.
Electrical Data
Operating voltage (primary) | 100-240V AC 48-63Hz |
Output voltage | 24V-28 DC adjustable, tolerance +/-3% |
Output current |
1.0A short-circuit proof and overload proof, electronically protected current limitation 1.7A short circuit current 2.2A |
Minimum load | 0 mA |
Residual ripple | 60 mVss |
No-load power loss | 0.4-0.5W |
Connection | screw terminals 2.5 mm² |
Operating temperature | -10...+50°C |
Storage temperature | -25...+70°C |
Humidity | 5...90 % r.h. non-condensing |
Protection class | in non-installed state IP20 |
New
Sale
NT24V/1,0A-S
Article no.: 80030010
The Power Supply Unit is used to supply the ISYGLT BUS components with operating voltage.