With the SUN Processor SUN-PRO-02, the integrated optional system clock, the Daylight Sensor ZTLS-04 and the Blind Control Module JSM-02C-230V-2A, a complex blind control with artificial light correction can be realised. External blinds can be protected by ice monitoring, wind and rain sensors. The blind module is used to control two separate blind motors and has extensive parameterisation options. The Daylight Sensor ZTLS-04 provides the current light values of the four cardinal directions.
The SUN-PRO-02 calculates the current position of the sun for blind control or circadian light control depending on the building position, date and time. It transfers two system variables for the azimuth value (direction from which the sun is currently shining) and elevation value (elevation angle of the sun from the horizon) of the current position of the sun to the Master. Now the Blind Module can set the slat angle for shading with the preset parameter settings and the actual light values from the Daylight Sensor.
Furthermore, the SUN-PRO-02 can be used for a sun position-guided colour temperature control. Based on the calculated position of the sun, the current colour value for the control of the luminaires can be determined.
New is that the SUN-PRO-02 now has an integrated, optionally activatable system clock and that the SUN-PRO-02 can be parameterised with the ProgramDesigner from version 8.00.17_R102.
Notice: The geographical position of the building to be controlled is set by parameter via the programming software ProgramDesigner.
Technical Data
Electrical Data
Operating voltage | 12V to 35V DC |
Current consumption | 24V = 20mA |
Subnet (RS-485) | max. 5.6V limitation by Z-diodes |
Connection | screw terminals 1.5mm², pluggable, BUS connector |
Operating temperature | -10° to +50°C |
Storage temperature | -25° to +70°C |
Humidity | 0-85 % r. h. non-condensing |
Protection class | in non-installed state IP30 |
SUN-PRO-02
Article no.: 80085101