Skip to main content Skip to page footer

SUN Processor SUN-PRO-02

The SUN-PRO-02 calculates the current position of the sun depending on the building position, date and time. It can be used, for example, for complex blind control with artificial light correction or colour temperature control according to the position of the sun.

Quick Facts

  1. sun position calculation
  2. passes elevation/azimuth values to Master
  3. for complex blind controls
  4. for colour temperature controls
  5. now parameterisable via ProgramDesigner
  6. integrated system clock available (can be activated optionally)

With the SUN Processor SUN-PRO-02, the integrated optional system clock, the Daylight Sensor ZTLS-04 and the Blind Control Module JSM-02C-230V-2A, a complex blind control with artificial light correction can be realised. External blinds can be protected by ice monitoring, wind and rain sensors. The blind module is used to control two separate blind motors and has extensive parameterisation options. The Daylight Sensor ZTLS-04 provides the current light values of the four cardinal directions.

The SUN-PRO-02 calculates the current position of the sun for blind control or circadian light control depending on the building position, date and time. It transfers two system variables for the azimuth value (direction from which the sun is currently shining) and elevation value (elevation angle of the sun from the horizon) of the current position of the sun to the Master. Now the Blind Module can set the slat angle for shading with the preset parameter settings and the actual light values from the Daylight Sensor.

Furthermore, the SUN-PRO-02 can be used for a sun position-guided colour temperature control. Based on the calculated position of the sun, the current colour value for the control of the luminaires can be determined.

New is that the SUN-PRO-02 now has an integrated, optionally activatable system clock and that the SUN-PRO-02 can be parameterised with the ProgramDesigner from version 8.00.17_R102.

Notice: The geographical position of the building to be controlled is set by parameter via the programming software ProgramDesigner.

Technical Data

Electrical Data

Operating voltage 12V to 35V DC
Current consumption 24V = 20mA
Subnet (RS-485) max. 5.6V limitation by Z-diodes
Connection screw terminals 1.5mm², pluggable, BUS connector
Operating temperature -10° to +50°C
Storage temperature -25° to +70°C
Humidity 0-85 % r. h. non-condensing
Protection class in non-installed state IP30

Design, Dimensions, Weight

Design DIN rail-mounting plastic housing light grey, snap-on on 35mm DIN rail 3 HP
Dimensions WxHxD 53x90x59mm
Weight 90g

Ordering Data and Conformity

Type designation SUN-PRO-02
Article no. 80085101
Make ISYGLT
Conformity CE

Downloads

Tender Documents

Instruction Manuals

Wiring Diagrams

Commissioning and Configuration

Function Indicators (LEDs on the Module)

LED Designation State Meaning
red Power Off No operating voltage
On Operating voltage, no error
yellow BUS Off / On Error BUS
Blinking Interference-free data transmission via the BUS line

Pin Assignment

4-pole plug below

=Ub Operating voltage
0V 0V Operating voltage
A BUS A (subnet RS-485)
B BUS B (subnet RS-485)

2x P-COM ports

P-COM Subnet and operating voltage