Skip to main content Skip to page footer

Analog Module AD-04P-V2

Analog input module with 4 potentiometers on the module. 
The individual analog channels are available in the master module for further links, depending on the application.

Quick Facts

  • 4 analog inputs (4 potentiometers on module)
  • 8 bit resolution per channel
  • setpoint setting
  • dimming value setting
  • comparison value setting

The parameterization module is used to enter 4 set values with definable value ranges such as 0-100%, 0-255 up to 0-65535. The set values are set for each channel using a separate potentiometer integrated in the module. The resolution of each channel is 8 or 12 bits. The individual analog channels are available in the master module for further linking, depending on the application.

Type designation AD-04P-V2
Article no. 80027310
Operating voltage 17V-35V DC
Current consumption 21mA at 24V
Subnet (RS-485) max. 5.6V limitation by Z-diodes
Connection screw terminals pluggable
Operating temperature -10...+50°C
Storage temperature -25...+70°C
Humidity 0...85% r.h. non-condensing
Protection class IP30
Design DIN rail-mounting plastic housing light grey, snap-on on 35mm DIN rail 3 HP
Dimensions WxHxD 53x90x59mm
Weight 120g
Make ISYGLT
Conformity CE

Tender Documents

Instruction Manuals

Wiring Diagrams

DIP switch

8-pole DIP switch for setting the ISYGLT BUS address (0-127) is located under the cover of the module.

DIPSetting
S1Reserve (must be set to OFF)
S2 bis S8ISYGLT Modul address

Function Indicators (LEDs on the Module)

LEDDesignationStateMeaning
redPowerOffNo operating voltage
OnOperating voltage, no error
yellowBUSOffError BUS
OnBUS transmission is active, but the communication address was not recognized
blinkingInterference-free data transmission via the BUS line

Pin Assignment

4-pole plug top

=Ub Operating voltage
0V 0V Operating voltage
A BUS A (Subnet RS-485)
B BUS B (Subnet RS-485)

2x P-COM connectors

P-COM Subnet and operating voltage
New Sale
AD-04P-V2_aimeos.jpg

AD-04P-V2

Article no.: 80027310

Analog input module for entering 4 target values with definable value ranges such as 0-100%, 0-255 up to 0-65535. The target values are adjusted for each channel via a separate potentiometer integrated in the module. The resolution of each channel is 8 or 12 bits.