Skip to main content Skip to page footer

DALI Module DALI-16B-2X

DALI module with 2 separate DALI lines for controlling up to 2 x 64 DALI lights. Each of these 64 DALI devices is programmed with a unique device address. One of 16 ISYGLT dimming groups per DALI line can be assigned to this device address by parameterising the DALI-16B-2X module.

Quick Facts

  • up to 2 x 16 groups
  • up to 2 x 64 DALI participants
  • supports DT6 and DT8
  • group allocation freely parameterisable
  • DALI broadcast for commissioning and emergency operation
  • test and emergency operation option with ON/OFF button
  • DALI-2 motion detector evaluation
  • DALI-2 emergency lighting test and evaluation
  • ECG addressing and checking in conjunction with the IP Master and the DALI Web Plugin

The DALI-16B-2X module is used to control electronic ballasts for LEDs that communicate using the DALI protocol. Up to 64 DALI ECGs (electronic ballasts) can be operated on each of the two DALI lines. Each of these 64 DALI devices must be programmed with a unique device address (DALI short address). Each device address can be assigned one of 16 ISYGLT dimming groups by parameterising the DALI-16B-2X module. These dimming groups are controlled directly in the ISYGLT system via value variables (flags).

The module is equipped with its own mains supply. This enables a freely configurable emergency function for the corresponding DALI BUS. All DALI output devices are fully integrated into the possibilities of the ISYGLT system thanks to our concept. This means that the full range of functions of the ISYGLT system is available.
The module occupies 2 module addresses on the BUS.

With the DALI modules of the DALI-16B-2X series, a new DALI gateway concept has been realised that offers many more possibilities.

Functions:

  • DALI broadcast
  • DALI DT6, brightness, RGB (3xDT6), RGBW (4xDT6), HCL (2xDT6)
  • DALI DT8, HCL, RGB, RGBW
  • Optional
    - DALI-2 motion sensors, evaluation of up to 16 motion sensors in 7 groups
    - DALI-2 emergency lighting functionality with test functions, evaluation of results and errors
  • DALI broadcast for commissioning and emergency operation via button ON/OFF
  • ECG addressing and checking in conjunction with the IP Master and the DALI-Web-Plugin

Type designation DALI-16B-2X
Article no. 80027165
Mains supply 198-264V AC, 198-280V DC, 0/50-60 Hz
Current consumption max. 95mA
Power consumption max. 10.5W +/- 10%
Insulation voltage 4000V ISYGLT, 1500V DALI / mains
Subnet (RS-485) max. 5.6V limitation by Z-diodes
DALI interface 2 separate DALI lines, output current max. 180mA per line
Connection Screw terminals 0.25mm² to 1.5mm²
Operating temperature -10°C to +50°C
Storage temperature -25°C to +70°C
Humidity 0-90% r.h. non-condensing
Protection class IP 20
Design DIN rail-mounting plastic housing light grey, snap-on on 35mm DIN rail 6 HP
Dimensions WxHxD 106x90x61mm
Weight 220g
Make ISYGLT
Conformity CE

Tender Documents

Instruction Manuals

DIP switch

8-pole DIP switch for setting the ISYGLT BUS address (0-127) is located under the cover of the module.

Special function DIP switch 1

DIPSetting
S1 OFFNormal operation
S1 ONEmergency / test operation with button on the module (ON / OFF)

Function Indicators (LEDs on the Module)

DesignationStatusColourMeaning
PowerOFF No operating voltage
ONredOperating voltage, no error
Flashingred/greenEmergency/test mode is active, DIP switch 1=ON
FlashingredBUS failure mode
BUS / Notb.DA1OFF No BUS detected, DIP switch 1=ON: emergency/test mode is active, button ON/OFF status DA1 OFF
ONyellowError BUS communication (address not detected)
FlashingyellowInterference-free data transmission via the BUS line
ONgreenDIP switch 1=ON: emergency/test mode is active, button ON/OFF status DA1 ON
Notb.DA2OFF DIP switch 1=ON: emergency/test mode is active, button ON/OFF status DA2 OFF
ONgreenDIP switch 1=ON: emergency/test mode is active, button ON/OFF status DA2 ON

Parameterisation with ProgrammDesigner

In the ISYGLT ProgrammDesigner there are various parameterisation options:

  • Grouping of the individual ECGs
  • Luminaire types DT6, DT8
  • Emergency lighting functionality or evaluation of motion detector
  • Emergency operation in case of BUS failure DALI and ISYGLT

Pin Assignment

9-pole plug below left

L Mains voltage 230V (50-60Hz)
N Neutral conductor
PE Protective conductor
DA1 + DALI BUS 1 + 
DA1 - DALI BUS 1 -
DA2 + DALI BUS 2 +
DA2 - DALI BUS 2 -
BUS A ISYGLT BUS A
BUS B ISYGLT BUS B

Additional Equipment


Variants

To top

New Sale
DALI-16B-2X.jpg

DALI-16B-2X

Article no.: 80027165

DALI module with 2 separate DALI lines for controlling up to 2x 64 DALI luminaires in max. 2x 16 dimming groups. Supports luminaire types DT6 and DT8.