Flush-mounting Input Module for connecting conventional pushbuttons and switches to the subnet. The module can be used to transfer 4 commands to the BUS system.

Quick Facts

  1. 4 digital inputs
  2. Connecting standard buttons
  3. Fits into a standard switch box

Design, Dimensions, Weight

Design encapsulated in yellow plastic cap for installation in commercially available flush-mounted boxes or third-party devices
Dimensions DxH 50x18mm
Weight approx. 90g

Ordering Data and Conformity

Type designation IN-04U
Article no. 80024040
Make ISYGLT
Conformity CE

Electrical Data

Operating voltage 12-27V DC
Current consumption 20mA
Inputs 4x 12-30V DC, 5mA (potential-free contact) via optocoupler (4.7kOhm)
Subnet (RS-485) max. 5.6V limitation by Z-diodes
Connection screw terminals 2.5mm² for BUS, solid wires 0.8mm for inputs
Operating temperature -10...+50°C
Storage temperature -25...+70°C
Humidity 0...85 % r.h. non-condensing
Protection class IP 20

Tender Documents

Instruction Manuals

Wiring Diagrams

Special function DIP switch 1

DIP-1 Setting
OFFData transmission rate 38400 Baud
ONData transmission rate 9600 Baud

 


Function Indicators (LEDs on the Module)

LEDDesignationStateMeaning
redPowerOffNo operating voltage
OnOperating voltage, no error
yellowBUSOffError BUS
blinkingInterference-free data transmission via the BUS line

Pin Assignment

4-pole connector

=Ub Operating voltage
0V 0V Operating voltage
A BUS A (Subnet RS-485)
B BUS B (Subnet RS-485)

5-pole wire connector

White Input 1
Brown Input 2
Green Input 3
Yellow Input 4
Red COM.A (+Ub-1V)

DIP switches

8-pole DIP switch for setting the ISYGLT BUS address (0-127) is located on the module.

The flush-mounting IN Module is used to connect conventional pushbuttons and switches to the subnet. The module can be used to transfer 4 commands to the BUS system. The buttons/switches are connected by means of pre-assembled wires.