Digital I/O Module I/O-44E

With the module up to 4 commands can be transferred to the BUS system and 4 signals can be output. The functions of the inputs and outputs are freely programmable.

Quick Facts

  1. 4 optocoupler inputs
  2. 4 transistor outputs PNP, 24V/1A
  3. Coupling of illuminated pushbuttons or magnetic valves
  4. For sanitary or climate control on site

The built-in I/O Module is used to connect illuminated pushbuttons or magnetic valves and buttons to the subnet. The module can be used to transfer 4 commands to the BUS system and output 4 signals. The buttons or magnetic valves are connected via 4-pole Molex connectors.

Example: (see wiring diagrams) 2 buttons with feedback signal and 2 buttons with 2 magnetic valves

Electrical Data

Operating voltage 12V to 35V DC
Current consumption 20mA to 4A depending on output load
Inputs 4x 12-30V DC, 5mA (potential-free contact) via optocoupler (4.7kOhm)
Outputs 4x +Ub -2V, max. 1A via PNP transistor outputs short-circuit-proof
Subnet (RS-485) max. 5.6V limitation by Z-diodes
Connection screw terminals 2.5mm² for BUS, inputs/outputs via 4-pole P-COM / Molex connectors
Operating temperature -10...+50°C
Storage temperature -25...+70°C
Humidity 0...85 % r.h. non-condensing
Protection class IP20

Design, Dimensions, Weight

Design encapsulated in black plastic housing for installation in third-party devices, loose or by means of 2 screw fixings
Dimensions WxHxD 70x50x37mm
Weight approx. 200g

Ordering Data and Conformity

Type designation I/O-44E
Article no. 80021244
Make ISYGLT
Conformity CE

Tender Documents

Instruction Manuals

Wiring Diagrams

DIP switches

8-pole DIP switch for setting the ISYGLT BUS address (0-127) is located on the module.

Special function DIP switch 1

DIP-1 Setting
OFFData transmission rate 38400 Baud
ONData transmission rate 9600 Baud

Function Indicators (LEDs on the Module)

LED DesignationState Meaning
red POWEROff No operating voltage
OnOperating voltage, no error
yellowBUSOff / OnError BUS
blinkingInterference-free data transmission via the BUS line
4x green Channel 1-4Off Output inactive
On Output active

Pin Assignment

8-pole terminal

Ub Operating voltage
Ub Operating voltage
0V Operating voltage 0V
0V Operating voltage 0V
A Subnet (BUS A, RS-485)
A Subnet (BUS A, RS-485)
B Subnet (BUS B, RS-485)
B Subnet (BUS B, RS-485)

4x 4-pole P-COM / Molex plug connectors

A1 Output 1 A2 Output 2 A3 Output 3 A4 Output 4
0V Output 1 0V Output 2 0V Output 3 0V Output 4
E1 Input 1 E2 Input 2 E3 Input 3 E4 Input 4
0V Input 1 0V Input 2 0V Input 3 0V Input 4