The ISYGLT-DSI/DALI-03B Module is used to control ECGs for fluorescent lamps and low voltage transformers which can communicate with the digital DSI or DALI signal. The module has 3 separate DSI/DALI interfaces. A maximum of 64 DSI/DALI standard loads (2mA) can be connected to one DSI/DALI channel. The power supply of the module can drive a maximum of 150 DSI standard loads (all 3 DSI/DALI channels).
All switching and dimming functions can be implemented digitally with the DSI/DALI signal. The module has its own mains supply. This enables a freely configurable emergency function for the 3 DSI/DALI outputs.
The ProgramDesigner can be used to parameterise whether the 3 channels of the module should work in DSI or DALI (broadcast) operation.
The following functions can be performed independently by the DSI/DALI Module:
- Calculation of increases with time constants from 0.5 seconds to 18 hours
- Independent regulation of instantaneous analog ACTUAL values to preset analog SETPOINT values at a preset speed (optional in preset time)
- Feedback of the termination of the analog value output after the execution of time functions
- Stop function during the execution of time functions
- OVERSAMPLING error correction (With the so-called "OVERSAMPLING", the DSI/DALI Module automatically corrects the jumps in the analog values caused by the cycle times of the BUS system. For this purpose, the analog values between the BUS cycles are transformed back into the resolution of 8 bits by linearisation.)
- Execution of blinking functions
Electrical Data
Mains supply | 230V / 50-60 Hz |
Current consumption | 15mA |
Output | 3 x DSI/DALI BUS, max. 64 devices each, total however max. 150 devices (standard loads 2mA per device) |
Insulation voltage | 3500V (ISYGLT, DSI/DALI / mains) |
Subnet (RS-485) | max. 5.6V limitation by Z-diodes |
Connection | screw terminals 1.5mm² pluggable |
Operating temperature | -10...+50°C |
Storage temperature | -25...+70 °C |
Humidity | 0...85 % r. h. non-condensing |
Protection class | IP 30 |
Function Indicators (LEDs on the Module)
LED | Designation | State | Meaning |
---|---|---|---|
red | Power | Off | No operating voltage |
On | Operating voltage, no error | ||
yellow | BUS | Off | BUS wiring error |
On | Error BUS communication (address) | ||
blinking | Interference-free data transmission via the BUS line | ||
2x green | P1 / P2 | blinking in alternation | No parameter data in the module |
P1 On | Potentiometer 1 is active | ||
P2 On | Potentiometer 2 is active |
DSI/DALI-03B
Article no.: 80027103